Current Transformers
Current transformer ratio selection and efficiency require unique consideration when applying transformer safety. Unique factors related to transformers, including its winding ratios, magnetizing inrush present, and the presence of winding faucets or load tap changers, are supplys of troublesomeies in engineering a loyal and steady protection scheme for the transformer.
Errors attributable to CT saturation and load-tap-changers are in particular very important for differential protection schemes the place the presents from a couple of set of CTs are when compared. To catch up on the saturation=mismatch blunders, overcurrent relays have to be set to function above these error.
CT Current Mismatch
Under normal, non-fault conditions, a transformer differential relay ought to ideally have equivalent presents in the secondaries of all current transformers linked to the relay in order that no present would drift in its working coil. It is tough, on the different hand, to match current transformer ratios exactly to the transformer winding ratios. This activity grow to bes not possible with the presence of transformer off-load and on-load faucets or load tap changers that vary the voltage ratios of the transformer windings depending on machine voltage and transformer loading.
The excessiveest 2ndary current mismatch between all present transformers linked within the differential scheme have to be calculated when selecting the relay operating environment. If time lengthened overcurrent protection is used, the time prolong atmosphere must also be based on the same consideration. The mismatch calculation needs to be performed for maximum load and through-fault stipulations.
CT Saturation
CT saturation can have a poor affect on the power of the transformer safety to function for inner faults (dependability) and to no longer operate for external faults (security).
For internal faults, dependability of the harmonic restraint type relays will be terriblely impacted if current harmonics generated within the CT secondary circuit due to CT saturation are excessive sufficient to restrain the relay. With a saturated CT, 2nd and 3rd harmonics predominate firstly, however the even harmonics progressively disappear with the decay of the DC element of the fault present. The relay may then function sooner or later when the restraining harmonic part is decreased. These relays on an ordinary basis embody an immediate overcurrent point that's now not restrained with the help of harmonics, however is ready very high (typically 20 times transformer rating). This element may operate on severe inside faults.
For exterior faults, safety of the differentially connected transformer safety may be jeopardized if the present transformers’ unequal saturation is extreme sufficient to produce error present above the relay surroundings. Relays geared up with restraint windings in each and every present transformer circuit would be safer.
The safety downside is particularly crucial when the present transformers are connected to bus breakers quite than the transformer itself. External faults on this case will be of very excessive magnitude as they are not restricted by means of the transformer impedance.
Magnetizing Inrush (Initial, Recovery, Sympathetic)
Initial
When a transformer is energized after being de-energized, a transient magnetizing or thrilling present that will reach instantaneous heights of up to 30 instances full load present may just go with the flow.
This can cause operation of overcurrent or differential relays defending the transformer. The magnetizing current flows in just one winding, for this reason it's going to seem to a differentially related relay as an internal fault.
Techniques used to prevent differential relays from operating on inrush embody discoverion of present harmonics and 0 present intervals, each being traits of the magnetizing inrush current. The former takes advantage of the presence of harmonics, particularly the second harmonic, within the magnetizing inrush present to restrain the relay from operation. The latter differentiates between the fault and inrush currents by way of measuring the zero current periods, with the intention to be for a lot longer for the inrush than for the fault present.
Recovery Inrush
A magnetizing inrush current may additionally waft if a voltage dip is followed by restoration to standard voltage.
Typically, this happens upon elimination of an exterior fault. The magnetizing inrush is frequently less severe on this case than in preliminary energization as the transformer was to no longertally de-energized previous to voltage recovery.
Sympathetic Inrush
A magnetizing inrush present can float in an energized transformer when a nearby transformer is energized. The offset inrush current of the financial institution being energized will discover a parallel path within the energized bank. Again, the magnitude is regularly less than the case of initial inrush. Both the recovery and sympathetic inrush phenomena recommend that restraining the transformer protection on magnetizing inrush current is required at all instances, not most effective when switching the transformer in carrier after a interval of de-energization.
Primary-Secondary Phase-Shift
For transformers with usual delta-wye connections, the presents on the delta and wye sides will have
a 308phase shift relative to one another. Current transformers used for traditional differential relays must
be linked in wye-delta (opposite of the transformer winding connections) to catch up on the
transformer section shift.
Phase correction is regularly insidely equipped in microprocessor transformer protection relays via
software virtual interposing CTs for every transformer winding and, as with the ratio correction, will
depend upon the selected configuration for the restrained inputs. This permits the primary current
transformers to all be related in wye.
Turn-to-Turn Faults
Fault currents on account of a turn-to-turn fault have low magnitudes and are laborious to discover. Typically, the fault must evolve and have an effect on a just right section of the winding or arc over to other sections of the transformer ahead of being noticeed by means of overcurrent or differential protection relays.
For early noticeion, reliance is usually made on tools that can measure the ensuing accumulation of fuel or changes in power within the transformer tank.
Through Faults
Through faults could have an effect on each the transformer and its protection scheme. Depending on their severity, frequency, and duration, via fault presents can result in mechanical transformer harm, even though the fault is just a little limited through the transformer impedance.
For transformer differential protection, present transformer mismatch and saturation could produce operating currents on through faults. This need to be taken into consideration when choosing the scheme, current transformer ratio, relay sensitivity, and running time. Differential protection schemes geared up with restraining windings offer better security for these via faults.
Backup Protection
Backup safety, generally overcurrent or impedance relays applied to at least one or either facet of the transformer, carry out two performs. One perform is to againup the principle safety, most likely a differential relay, and operate in adventure of its failure to commute.
The second operate is safety for thermal or mechanical injury to the transformer. Protection that may become mindful of these external faults and operate in time to prevent transformer harm needs to be considered. The protection must be set to operate ahead of the thru-fault stand up to capability of the transformer is reached.If, on account of its large measurement or significance, most effective differential protection is applied to a transformer, clearing of external faults earlier than transformer damage can occur by other protective tools have to be ensured
Home » transformer » Special Considerations for Transformer Protections